 ModbusTCP registers for Tx5xx/Tx6xx (T3511, T4511, T7511, T2514, T0510, T3510,
                                      T7510, T5540, T6540, T5541, T6541, T0610,
                                      T4611, T3610, T3611, T7610, T7611, T6640,
                                      T5640, T5545, T6545, T7613, T5641, T6641)
 standard ModbusTCP port: 502

 v3.2 for firmware 1-5-7.4 and 1-5-7.5, 2017-11-24
 ModbusTCP specification is free available: http://modbus.org/specs.php
--------------------------------------------------------------------------------


List of Supported Modbus commands
--------------------------------------------------------------------------------

|-----------------------------------------|--------|---------------------------|
| Command                                 | Code   | Description               |
|                                         | [HEX]  |                           |
|-----------------------------------------|--------|---------------------------|
| Read Holding Register(s)                | 0x03   | Reads 16 bit register(s)  |
|-----------------------------------------|--------|---------------------------|


Measured values
--------------------------------------------------------------------------------

|-----------------------|--------|--------|--------|---------------------------|
| Variable              | Adr.   | Adr.   | Type*) | Description               |
|                       | [HEX]  | [DEC]  |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| temperature           | 0x0031 | 49     | Int*10 | unit [C] or [F]         |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| reletive humidity     | 0x0032 | 50     | Int*10 | unit [%RH]                |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| computed value (CV)   | 0x0033 | 51     | Int*10 | units depends on computed |
|                       |        |        |        | value **)                 |
|-----------------------|--------|--------|--------|---------------------------|
| atmospheric pressure  | 0x0034 | 52     | Int*X  | units depends on selected |
| or                    |        |        |        | pressure units or device  |
| CO2 level (P/CO2)     |        |        |        | type ***)                 |
|-----------------------|--------|--------|--------|---------------------------|

|-----------------------|--------|--------|--------|---------------------------|
| dew point temperature | 0x0035 | 53     | Int*10 | unit [C] or [F]         |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| absolute humidity     | 0x0036 | 54     | Int*10 | unit [g/m^3]              |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| Specific humidity     | 0x0037 | 55     | Int*10 | unit [g/kg]               |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| mixing ratio          | 0x0038 | 56     | Int*10 | unit [g/kg]               |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| specific enthalpy     | 0x0039 | 57     | Int*10 | unit [kJ/kg]              |
|                       |        |        |        |                           |
|-----------------------|--------|--------|--------|---------------------------|


Device identification
--------------------------------------------------------------------------------

|-----------------------|--------|--------|--------|---------------------------|
| Variable              | Adr.   | Adr.   | Type*) | Description               |
|                       | [HEX]  | [DEC]  |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| serial number high    | 0x1035 | 4149   | BCD    | unique serial number have |
| serial number low     | 0x1036 | 4150   | BCD    | 8 digits                  |
|-----------------------|--------|--------|--------|---------------------------|
| device type           | 0x1037 | 4151   | HEX    |                           |
|-----------------------|--------|--------|--------|---------------------------|


Alarm status and limits
--------------------------------------------------------------------------------

|-----------------------|--------|--------|--------|---------------------------|
| Variable              | Adr.   | Adr.   | Type*) | Description               |
|                       | [HEX]  | [DEC]  |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| temper. low limit     | 0x5001 | 20481  | Int*10 |                           |
| temper. high limit    | 0x5002 | 20482  | Int*10 |                           |
| humidity low limit    | 0x5003 | 20483  | Int*10 |                           |
| humidity high limit   | 0x5004 | 20484  | Int*10 |                           |
| CV low limit          | 0x5005 | 20485  | Int*10 |                           |
| CV high limit         | 0x5006 | 20486  | Int*10 |                           |
| temper. hysteresis    | 0x5007 | 20487  | Int*10 |                           |
| temper. time delay    | 0x5008 | 20488  | DEC    | Unit [s]                  |
| humidity hysteresis   | 0x5009 | 20489  | Int*10 |                           |
| humidity time delay   | 0x500A | 20490  | DEC    | Unit [s]                  |
| CV hysteresis         | 0x500B | 20491  | Int*10 |                           |
| CV time delay         | 0x500C | 20492  | DEC    | Unit [s]                  |
| temepr. alarm status  | 0x500D | 20493  | String | "hi", "lo", "no"          |
| humidity alarm status | 0x500E | 20494  | String | "hi", "lo", "no"          |
| CV alarm status       | 0x500F | 20495  | String | "hi", "lo", "no"          |
| P/CO2 low  limit      | 0x5010 | 20496  | Int*X  |                           |
| P/CO2 high limit      | 0x5011 | 20497  | Int*X  |                           |
| P/CO2 hysteresis      | 0x5012 | 20498  | Int*X  |                           |
| P/CO2 alarm status    | 0x5013 | 20499  | String | "hi", "lo", "no"          |
| P/CO2 time delay      | 0x5014 | 20500  | DEC    | Unit [s]                  |
|-----------------------|--------|--------|--------|---------------------------|


MinMax memory registers (new registers for fw 1-5-6-x)
--------------------------------------------------------------------------------

|-----------------------|--------|--------|--------|---------------------------|
| Variable              | Adr.   | Adr.   | Type*) | Description               |
|                       | [HEX]  | [DEC]  |        |                           |
|-----------------------|--------|--------|--------|---------------------------|
| temper. min value     | 0x5015 | 20501  | Int*10 |                           |
| temper. max value     | 0x5016 | 20502  | Int*10 |                           |
| humidity min value    | 0x5017 | 20503  | Int*10 |                           |
| humidity max value    | 0x5018 | 20504  | Int*10 |                           |
| CV min value          | 0x5019 | 20505  | Int*10 |                           |
| CV max value          | 0x501A | 20506  | Int*10 |                           |
| P/CO2 min value       | 0x501B | 20507  | Int*X  |                           |
| P/CO2 min value       | 0x501C | 20508  | Int*X  |                           |
|-----------------------|--------|--------|--------|---------------------------|


Notice
--------------------------------------------------------------------------------

*)  Type:
     
    DEC ...... decadic number in range 0 - 4500 (16bit)
    BCD ...... register is in BCD format (16bit)
    HEX ...... number in HEX format (16bit)
    String ... two characters in one 16bit register:
               "no" ... none
               "hi" ... high alarm
               "lo" ... low alarm
    Int*10 ... register is in format integer*10 (16bit); 125=12.5C;
               error1=9999, error2=-9999, n/a=-9998
    Int*X .... register format depends on value type; error2=-9999, n/a=-9998
               Atmospheric pressure ***):
                   hPa ...... integer*10;   9760  = 976.0hPa
                   PSI ...... integer*1000; 14156 = 14.156PSI
                   inHg ..... integer*100;  2882  = 28.82inHg
                   mBar ..... integer*10;   9761  = 976.1mBar
                   oz/in2 ... integer*10;   2265  = 226.5oz/in2
                   mmHg ..... integer*10;   7321  = 732.1mmHg
                   inH2O .... integer*10;   3919  = 391.9inH2O
                   kPa ...... integer*100;  9761  = 97.61kPa
               CO2 level:
                   ppm ...... integer;      897   = 897ppm

**) Supported Computed values:

    Dew point temperature ... C or F
    Absolute humidity ....... g/m^3
    Specific humidity ....... g/kg
    Mixing ratio ............ g/kg